"group": {
"desc": "Dynamic Reactive Current ",
"label": "Dynamic Reactive Current",
"name": "reactive_current",
"points": [
{
"desc": "Model identifier",
"label": "Model ID",
"mandatory": "M",
"name": "ID",
"size": 1,
"static": "S",
"type": "uint16",
"value": 128
},
{
"desc": "Model length",
"label": "Model Length",
"mandatory": "M",
"name": "L",
"size": 1,
"static": "S",
"type": "uint16"
},
{
"access": "RW",
"desc": "Indicates if gradients trend toward zero at the edges of the deadband or trend toward zero at the center of the deadband.",
"label": "ArGraMod",
"mandatory": "M",
"name": "ArGraMod",
"size": 1,
"symbols": [
{
"name": "EDGE",
"value": 0
},
{
"name": "CENTER",
"value": 1
}
],
"type": "enum16"
},
{
"access": "RW",
"desc": "The gradient used to increase capacitive dynamic current. A value of 0 indicates no additional reactive current support.",
"label": "ArGraSag",
"mandatory": "M",
"name": "ArGraSag",
"sf": "ArGra_SF",
"size": 1,
"type": "uint16",
"units": "%ARtg/%dV"
},
{
"access": "RW",
"desc": "The gradient used to increase inductive dynamic current. A value of 0 indicates no additional reactive current support.",
"label": "ArGraSwell",
"mandatory": "M",
"name": "ArGraSwell",
"sf": "ArGra_SF",
"size": 1,
"type": "uint16",
"units": "%ARtg/%dV"
},
{
"access": "RW",
"desc": "Activate dynamic reactive current model",
"label": "ModEna",
"mandatory": "M",
"name": "ModEna",
"size": 1,
"symbols": [
{
"name": "ENABLED",
"value": 0
}
],
"type": "bitfield16"
},
{
"access": "RW",
"desc": "The time window used to calculate the moving average voltage.",
"label": "FilTms",
"name": "FilTms",
"size": 1,
"type": "uint16",
"units": "Secs"
},
{
"access": "RW",
"desc": "The lower delta voltage limit for which negative voltage deviations less than this value no dynamic vars are produced.",
"label": "DbVMin",
"name": "DbVMin",
"sf": "VRefPct_SF",
"size": 1,
"type": "uint16",
"units": "% VRef"
},
{
"access": "RW",
"desc": "The upper delta voltage limit for which positive voltage deviations less than this value no dynamic current produced.",
"label": "DbVMax",
"name": "DbVMax",
"sf": "VRefPct_SF",
"size": 1,
"type": "uint16",
"units": "% VRef"
},
{
"access": "RW",
"desc": "Block zone voltage which defines a lower voltage boundary below which no dynamic current is produced.",
"label": "BlkZnV",
"name": "BlkZnV",
"sf": "VRefPct_SF",
"size": 1,
"type": "uint16",
"units": "% VRef"
},
{
"access": "RW",
"desc": "Hysteresis voltage used with BlkZnV.",
"label": "HysBlkZnV",
"name": "HysBlkZnV",
"sf": "VRefPct_SF",
"size": 1,
"type": "uint16",
"units": "% VRef"
},
{
"access": "RW",
"desc": "Block zone time the time before which reactive current support remains active regardless of how low the voltage drops.",
"label": "BlkZnTmms",
"name": "BlkZnTmms",
"size": 1,
"type": "uint16",
"units": "mSecs"
},
{
"access": "RW",
"desc": "Hold time during which reactive current support continues after the average voltage has entered the dead zone.",
"label": "HoldTmms",
"name": "HoldTmms",
"size": 1,
"type": "uint16",
"units": "mSecs"
},
{
"desc": "Scale factor for the gradients.",
"label": "ArGra_SF",
"mandatory": "M",
"name": "ArGra_SF",
"size": 1,
"type": "sunssf"
},
{
"desc": "Scale factor for the voltage zone and limit settings.",
"label": "VRefPct_SF",
"name": "VRefPct_SF",
"size": 1,
"type": "sunssf"
},
{
"name": "Pad",
"size": 1,
"type": "pad"
}
],
"type": "group",
"detail": "Ref 3: 8.10.1.2; Ref 4: 12"
},
"id": 128
}