pub enum WindLookupTableFunctionKind {
Show 16 variants
prr,
omegap,
ipmax,
iqmax,
pwp,
tcwdu,
tduwt,
qmaxp,
qminp,
qmaxu,
qminu,
tuover,
tuunder,
tfover,
tfunder,
qwp,
}Expand description
Function of the lookup table.
Variants§
prr
Power versus speed change (negative slip) lookup table (prr(deltaomega)). It is used for the rotor resistance control model, IEC 61400-27-1:2015, 5.6.5.3.
omegap
Power vs. speed lookup table (omega(p)). It is used for the P control model type 3, IEC 61400-27-1:2015, 5.6.5.4.
ipmax
Lookup table for voltage dependency of active current limits (ipmax(uWT)). It is used for the current limitation model, IEC 61400-27-1:2015, 5.6.5.8.
iqmax
Lookup table for voltage dependency of reactive current limits (iqmax(uWT)). It is used for the current limitation model, IEC 61400-27-1:2015, 5.6.5.8.
pwp
Power vs. frequency lookup table (pWPbias(f)). It is used for the wind power plant frequency and active power control model, IEC 61400-27-1:2015, Annex D.
tcwdu
Crowbar duration versus voltage variation look-up table (TCW(du)). It is a case-dependent parameter. It is used for the type 3B generator set model, IEC 61400-27-1:2015, 5.6.3.3.
tduwt
Lookup table to determine the duration of the power reduction after a voltage dip, depending on the size of the voltage dip (Td(uWT)). It is a type-dependent parameter. It is used for the pitch control power model, IEC 61400-27-1:2015, 5.6.5.1.
qmaxp
Lookup table for active power dependency of reactive power maximum limit (qmaxp(p)). It is used for the QP and QU limitation model, IEC 61400-27-1:2015, 5.6.5.10.
qminp
Lookup table for active power dependency of reactive power minimum limit (qminp(p)). It is used for the QP and QU limitation model, IEC 61400-27-1:2015, 5.6.5.10.
qmaxu
Lookup table for voltage dependency of reactive power maximum limit (qmaxu(p)). It is used for the QP and QU limitation model, IEC 61400-27-1:2015, 5.6.5.10.
qminu
Lookup table for voltage dependency of reactive power minimum limit (qminu(p)). It is used for the QP and QU limitation model, IEC 61400-27-1:2015, 5.6.5.10.
tuover
Disconnection time versus over-voltage lookup table (Tuover(uWT)). It is used for the grid protection model, IEC 61400-27-1:2015, 5.6.6.
tuunder
Disconnection time versus under-voltage lookup table (Tuunder(uWT)). It is used for the grid protection model, IEC 61400-27-1:2015, 5.6.6.
tfover
Disconnection time versus over-frequency lookup table (Tfover(fWT)). It is used for the grid protection model, IEC 61400-27-1:2015, 5.6.6.
tfunder
Disconnection time versus under-frequency lookup table (Tfunder(fWT)). It is used for the grid protection model, IEC 61400-27-1:2015, 5.6.6.
qwp
Look up table for the UQ static mode (qWP(uerr)). It is used for the voltage and reactive power control model, IEC 61400-27-1:2015, Annex D.
Implementations§
Trait Implementations§
Source§impl Clone for WindLookupTableFunctionKind
impl Clone for WindLookupTableFunctionKind
Source§fn clone(&self) -> WindLookupTableFunctionKind
fn clone(&self) -> WindLookupTableFunctionKind
1.0.0 (const: unstable) · Source§fn clone_from(&mut self, source: &Self)
fn clone_from(&mut self, source: &Self)
source. Read more