Skip to main content

Crate bacnet_objects

Crate bacnet_objects 

Source
Expand description

§bacnet-objects

Build BACnet object state with traits::BACnetObject and database::ObjectDatabase in the Rusty BACnet workspace. The database owns registered objects and supports identifier-based lookup; object modules provide their property implementations.

The crate has no Tokio dependency. Using it alone does not start a transport, a server executor or event/COV delivery.

§Features

ProfileFeaturesWhat it has
Hostedstd (default)Everything, including the file persistence backends (FileAuditLogPersistence, FileLogPersistence and the others), a writer thread per saving object, and tracing.
no_std with a heapalloc (without std)Every object type, the database and the persistence traits, for a target with a global allocator and atomic compare-and-swap (#1615). A save runs on the caller’s thread, and the application supplies the storage.

There is no build with neither feature: the database boxes every object, so a heap-free device answers from a static table instead. ARMv6-M (thumbv6m-none-eabi) lacks compare-and-swap, which alloc::sync::Arc needs, so the crate doesn’t build there. The design note has the details.

§Initialize and read an object

Place an application directory beside a checkout named rusty-bacnet, then add this dependency block to the application’s Cargo.toml. These are development-source paths, not a claim that the shown APIs are published; adjust the paths if your directories differ.

[dependencies]
bacnet-objects = { path = "../rusty-bacnet/crates/bacnet-objects" }
bacnet-types = { path = "../rusty-bacnet/crates/bacnet-types" }

Save this complete program as src/main.rs. It initializes an unattached Analog Input, transfers it to the database, then checks the stored identity, Present_Value and a missing-object lookup.

use bacnet_objects::analog::AnalogInputObject;
use bacnet_objects::database::ObjectDatabase;
use bacnet_types::enums::{EngineeringUnits, ObjectType, PropertyIdentifier};
use bacnet_types::primitives::{ObjectIdentifier, PropertyValue};

fn main() -> Result<(), bacnet_types::error::Error> {
    let object = ObjectIdentifier::new(ObjectType::ANALOG_INPUT, 7)?;
    let mut analog = AnalogInputObject::new(
        7,
        "supply-temperature",
        EngineeringUnits::DEGREES_CELSIUS,
    )?;
    analog.set_present_value(42.0);
    let mut database = ObjectDatabase::new();
    database.add(Box::new(analog))?;

    let stored = database.get(&object).expect("the object was registered");
    assert_eq!(stored.object_identifier(), object);
    assert_eq!(stored.object_name(), "supply-temperature");
    assert_eq!(
        stored.read_property(PropertyIdentifier::PRESENT_VALUE, None)?,
        PropertyValue::Real(42.0),
    );
    let absent = ObjectIdentifier::new(ObjectType::ANALOG_INPUT, 8)?;
    assert!(database.get(&absent).is_none());
    Ok(())
}

The direct setter above initializes an object before ownership transfer. AnalogInputObject::set_present_value bypasses running-server ownership, validation, intrinsic-event and COV processing. For live server updates, use BACnetServer::set_present_value_local and its documented policy instead of mutating a database object directly.

§Device identity and executor ownership

Use DeviceIdentity and device_identity::build_database_with_extra when assembling a server database. The helper installs the Device and configured Network Ports, and seeds the Device’s Object_List with the extra application objects. Adding a standalone analog object alone does not create a Device.

Objects read through a raw database return standalone state. A running BACnetServer supplies live executor-owned Device properties and lists through read_local; its shared database handle is not an equivalent live view. Never hold a database guard across network operations or shutdown. Durable objects can queue saves, so their final drop or the server’s explicit stop may wait on storage; this example uses only an in-memory Analog Input.

The example establishes local object initialization, lookup and property access. It does not establish transport operation, event delivery, physical equipment behavior, timing or standards conformance. Consult each object’s property and service documentation for its supported behavior.

§Documentation profile

This README is included as the crate landing page and the program runs as a doctest. The docs.rs profile disables defaults, explicitly selects std and targets x86_64-unknown-linux-gnu, so it shows the hosted API, the file persistence backends included; it does not render the alloc-only build, and a local render does not establish a docs.rs deployment.

Re-exports§

pub use device_identity::DeviceIdentity;

Modules§

access_control
Access Control objects (ASHRAE 135-2020 Clause 12).
accumulator
Accumulator (type 23) and Pulse Converter (type 24) objects.
analog
Analog Input (type 0), Analog Output (type 1), and Analog Value (type 2) objects.
audit
AuditLog (type 61) and AuditReporter (type 62) objects per Addendum 135-2016bj.
averaging
Averaging (type 18) object per ASHRAE 135-2020 Clause 12.5.
binary
Binary Input (type 3), Binary Output (type 4), and Binary Value (type 5) objects per ASHRAE 135-2020 Clauses 12.6, 12.7, and 12.8.
catalogue
The object catalogue: one object of each standard type this crate builds.
channel
Channel object (type 53) per ASHRAE 135-2020 Clause 12.53.
clock
Dependency-neutral clock data exposed to BACnet objects.
color
Color (type 63) and Color Temperature (type 64) objects, added by Addendum 135-2020ca (Clauses 12.X and 12.Y, Tables 12-X and 12-Y).
command
Command object (type 7) per ASHRAE 135-2020 Clause 12.10.
command_source
Explicit command origins and object-owned source tracking (Clause 19.5): per priority for a commandable Present_Value, and a single source for one with no priority array (#1552).
cov_change
The change test of COV reporting (Clause 13.1), shared by the server’s COV notifications and a Trend Log that logs by COV (#1480).
database
ObjectDatabase — stores and retrieves BACnet objects by identifier.
device
Device object (type 8) per ASHRAE 135-2020 Clause 12.11.
device_identity
Shared Device declarations and stock object construction.
durable
Saving object state off the object database lock (#1270).
elevator
Elevator Group, Escalator, and Lift objects per ASHRAE 135-2020.
event
Intrinsic reporting — OUT_OF_RANGE event state machine.
event_enrollment
EventEnrollment (type 9) object per ASHRAE 135-2020 Clause 12.12.
event_log
EventLog (type 25) object per ASHRAE 135-2020 Clause 12.27.
file
File (type 10) object per ASHRAE 135-2020 Clause 12.13.
group
Group, GlobalGroup, and StructuredView objects per ASHRAE 135-2020.
life_safety
Life Safety Point (type 21) and Life Safety Zone (type 22) objects per ASHRAE 135-2020 Clauses 12.15 and 12.16.
lighting
Lighting Output (type 54) and Binary Lighting Output (type 55) objects per ASHRAE 135-2020 Clauses 12.54 and 12.55.
load_control
Load Control object (type 28) per ASHRAE 135-2020 Clause 12.28.
log_buffer
Shared resident storage and identity projection for BACnet log objects.
log_persistence
Durable storage for the Trend Log, Trend Log Multiple and Event Log (#1541).
log_reporting
BUFFER_READY intrinsic reporting for the log objects (Clause 13.3.7).
loop_obj
Loop (type 12) object per ASHRAE 135-2020 Clause 12.17.
multistate
Multi-State Input (type 13), Multi-State Output (type 14), and Multi-State Value (type 19) objects per ASHRAE 135-2020 Clauses 12.18, 12.19, and 12.20.
network_port
Configured Network Port snapshots and selected live state (135-2020 Clause 12.56).
notification_class
NotificationClass object: priorities, acknowledgment requirements, and recipients.
notification_forwarder
Notification Forwarder object (type 51, Clause 12.51).
object_profile
The optional Tags, Profile_Location and Profile_Name rows (#1553).
present_value_access
How a Value object’s Present_Value is written.
program
Program object (type 16) per ASHRAE 135-2020 Clause 12.22.
property_metadata
Executable property metadata and compatibility projections.
schedule
Schedule (type 17) and Calendar (type 6) objects per ASHRAE 135-2020.
staging
Local-target Staging object (type 60) per ASHRAE 135-2020 Clause 12.62.
subscribed_recipients
A Notification Forwarder’s Subscribed_Recipients (Clause 12.51.9, #1049): a bounded BACnetLIST of BACnetEventNotificationSubscription whose entries lapse when their time runs out.
timer
Timer object (type 31) per ASHRAE 135-2020 Clause 12.57.
traits
BACnetObject trait — the interface all BACnet objects implement.
trend
TrendLog (type 20) and TrendLogMultiple (type 27) objects per ASHRAE 135-2020.
value_types