pub struct PssPTIST3 {Show 35 fields
pub base: PowerSystemStabilizerDynamics,
pub a0: Option<f64>,
pub a1: Option<f64>,
pub a2: Option<f64>,
pub a3: Option<f64>,
pub a4: Option<f64>,
pub a5: Option<f64>,
pub al: Option<f64>,
pub athres: Option<f64>,
pub b0: Option<f64>,
pub b1: Option<f64>,
pub b2: Option<f64>,
pub b3: Option<f64>,
pub b4: Option<f64>,
pub b5: Option<f64>,
pub dl: Option<f64>,
pub dtc: Option<f64>,
pub dtf: Option<f64>,
pub dtp: Option<f64>,
pub isw: Option<bool>,
pub k: Option<f64>,
pub lthres: Option<f64>,
pub m: Option<f64>,
pub nav: Option<f64>,
pub ncl: Option<f64>,
pub ncr: Option<f64>,
pub pmin: Option<f64>,
pub t1: Option<f64>,
pub t2: Option<f64>,
pub t3: Option<f64>,
pub t4: Option<f64>,
pub t5: Option<f64>,
pub t6: Option<f64>,
pub tf: Option<f64>,
pub tp: Option<f64>,
}Expand description
PTI microprocessor-based stabilizer type 3.
Fields§
§base: PowerSystemStabilizerDynamics§a0: Option<f64>Filter coefficient (A0).
a1: Option<f64>Limiter (Al).
a2: Option<f64>Filter coefficient (A2).
a3: Option<f64>Filter coefficient (A3).
a4: Option<f64>Filter coefficient (A4).
a5: Option<f64>Filter coefficient (A5).
al: Option<f64>Limiter (Al).
athres: Option<f64>Threshold value above which output averaging will be bypassed (Athres). Typical value = 0,005.
b0: Option<f64>Filter coefficient (B0).
b1: Option<f64>Filter coefficient (B1).
b2: Option<f64>Filter coefficient (B2).
b3: Option<f64>Filter coefficient (B3).
b4: Option<f64>Filter coefficient (B4).
b5: Option<f64>Filter coefficient (B5).
dl: Option<f64>Limiter (Dl).
dtc: Option<f64>Time step related to activation of controls (deltatc) (>= 0). Typical value = 0,025 (0,03 for 50 Hz).
dtf: Option<f64>Time step frequency calculation (deltatf) (>= 0). Typical value = 0,025 (0,03 for 50 Hz).
dtp: Option<f64>Time step active power calculation (deltatp) (>= 0). Typical value = 0,0125 (0,015 for 50 Hz).
isw: Option<bool>Digital/analogue output switch (Isw). true = produce analogue output false = convert to digital output, using tap selection table.
k: Option<f64>Gain (K). Typical value = 9.
lthres: Option<f64>Threshold value (Lthres).
m: Option<f64>(M). M = 2 x H. Typical value = 5.
Number of control outputs to average (NAV) (1 <= NAV <= 16). Typical value = 4.
ncl: Option<f64>Number of counts at limit to active limit function (NCL) (> 0).
ncr: Option<f64>Number of counts until reset after limit function is triggered (NCR).
pmin: Option<f64>(Pmin).
t1: Option<f64>Time constant (T1) (>= 0). Typical value = 0,3.
t2: Option<f64>Time constant (T2) (>= 0). Typical value = 1.
t3: Option<f64>Time constant (T3) (>= 0). Typical value = 0,2.
t4: Option<f64>Time constant (T4) (>= 0). Typical value = 0,05.
t5: Option<f64>Time constant (T5) (>= 0).
t6: Option<f64>Time constant (T6) (>= 0).
tf: Option<f64>Time constant (Tf) (>= 0). Typical value = 0,2.
tp: Option<f64>Time constant (Tp) (>= 0). Typical value = 0,2.