pub struct GovHydro2 {Show 30 fields
pub base: TurbineGovernorDynamics,
pub aturb: Option<f64>,
pub bturb: Option<f64>,
pub db1: Option<f64>,
pub db2: Option<f64>,
pub eps: Option<f64>,
pub gv1: Option<f64>,
pub gv2: Option<f64>,
pub gv3: Option<f64>,
pub gv4: Option<f64>,
pub gv5: Option<f64>,
pub gv6: Option<f64>,
pub kturb: Option<f64>,
pub mwbase: Option<f64>,
pub pgv1: Option<f64>,
pub pgv2: Option<f64>,
pub pgv3: Option<f64>,
pub pgv4: Option<f64>,
pub pgv5: Option<f64>,
pub pgv6: Option<f64>,
pub pmax: Option<f64>,
pub pmin: Option<f64>,
pub rperm: Option<f64>,
pub rtemp: Option<f64>,
pub tg: Option<f64>,
pub tp: Option<f64>,
pub tr: Option<f64>,
pub tw: Option<f64>,
pub uc: Option<f64>,
pub uo: Option<f64>,
}Expand description
IEEE hydro turbine governor with straightforward penstock configuration and hydraulic-dashpot governor.
Fields§
§base: TurbineGovernorDynamics§aturb: Option<f64>Turbine numerator multiplier (Aturb). Typical value = -1.
bturb: Option<f64>Turbine denominator multiplier (Bturb) (> 0). Typical value = 0,5.
db1: Option<f64>Intentional deadband width (db1). Unit = Hz. Typical value = 0.
db2: Option<f64>Unintentional deadband (db2). Unit = MW. Typical value = 0.
eps: Option<f64>Intentional db hysteresis (eps). Unit = Hz. Typical value = 0.
gv1: Option<f64>Nonlinear gain point 1, PU gv (Gv1). Typical value = 0.
gv2: Option<f64>Nonlinear gain point 2, PU gv (Gv2). Typical value = 0.
gv3: Option<f64>Nonlinear gain point 3, PU gv (Gv3). Typical value = 0.
gv4: Option<f64>Nonlinear gain point 4, PU gv (Gv4). Typical value = 0.
gv5: Option<f64>Nonlinear gain point 5, PU gv (Gv5). Typical value = 0.
gv6: Option<f64>Nonlinear gain point 6, PU gv (Gv6). Typical value = 0.
kturb: Option<f64>Turbine gain (Kturb). Typical value = 1.
mwbase: Option<f64>Base for power values (MWbase) (> 0). Unit = MW.
pgv1: Option<f64>Nonlinear gain point 1, PU power (Pgv1). Typical value = 0.
pgv2: Option<f64>Nonlinear gain point 2, PU power (Pgv2). Typical value = 0.
pgv3: Option<f64>Nonlinear gain point 3, PU power (Pgv3). Typical value = 0.
pgv4: Option<f64>Nonlinear gain point 4, PU power (Pgv4). Typical value = 0.
pgv5: Option<f64>Nonlinear gain point 5, PU power (Pgv5). Typical value = 0.
pgv6: Option<f64>Nonlinear gain point 6, PU power (Pgv6). Typical value = 0.
pmax: Option<f64>Maximum gate opening (Pmax) (> GovHydro2.pmin). Typical value = 1.
pmin: Option<f64>Minimum gate opening (Pmin) (< GovHydro2.pmax). Typical value = 0.
rperm: Option<f64>Permanent droop (Rperm). Typical value = 0,05.
rtemp: Option<f64>Temporary droop (Rtemp). Typical value = 0,5.
tg: Option<f64>Gate servo time constant (Tg) (> 0). Typical value = 0,5.
tp: Option<f64>Pilot servo valve time constant (Tp) (>= 0). Typical value = 0,03.
tr: Option<f64>Dashpot time constant (Tr) (>= 0). Typical value = 12.
tw: Option<f64>Water inertia time constant (Tw) (>= 0). Typical value = 2.
uc: Option<f64>Maximum gate closing velocity (Uc) (< 0). Unit = PU / s. Typical value = -0,1.
uo: Option<f64>Maximum gate opening velocity (Uo). Unit = PU / s. Typical value = 0,1.