pub struct GovHydro1 {Show 15 fields
pub base: TurbineGovernorDynamics,
pub at: Option<f64>,
pub dturb: Option<f64>,
pub gmax: Option<f64>,
pub gmin: Option<f64>,
pub hdam: Option<f64>,
pub mwbase: Option<f64>,
pub qnl: Option<f64>,
pub rperm: Option<f64>,
pub rtemp: Option<f64>,
pub tf: Option<f64>,
pub tg: Option<f64>,
pub tr: Option<f64>,
pub tw: Option<f64>,
pub velm: Option<f64>,
}Expand description
Basic hydro turbine governor.
Fields§
§base: TurbineGovernorDynamics§at: Option<f64>Turbine gain (At) (> 0). Typical value = 1,2.
dturb: Option<f64>Turbine damping factor (Dturb) (>= 0). Typical value = 0,5.
gmax: Option<f64>Maximum gate opening (Gmax) (> 0 and > GovHydro.gmin). Typical value = 1.
gmin: Option<f64>Minimum gate opening (Gmin) (>= 0 and < GovHydro1.gmax). Typical value = 0.
hdam: Option<f64>Turbine nominal head (hdam). Typical value = 1.
mwbase: Option<f64>Base for power values (MWbase) (> 0). Unit = MW.
qnl: Option<f64>No-load flow at nominal head (qnl) (>= 0). Typical value = 0,08.
rperm: Option<f64>Permanent droop (R) (> 0). Typical value = 0,04.
rtemp: Option<f64>Temporary droop (r) (> GovHydro1.rperm). Typical value = 0,3.
tf: Option<f64>Filter time constant (Tf) (> 0). Typical value = 0,05.
tg: Option<f64>Gate servo time constant (Tg) (> 0). Typical value = 0,5.
tr: Option<f64>Washout time constant (Tr) (> 0). Typical value = 5.
tw: Option<f64>Water inertia time constant (Tw) (> 0). Typical value = 1.
velm: Option<f64>Maximum gate velocity (Vlem) (> 0). Typical value = 0,2.