pub struct ExcDC3A1 {Show 15 fields
pub base: ExcitationSystemDynamics,
pub exclim: Option<bool>,
pub ka: Option<f64>,
pub ke: Option<f64>,
pub kf: Option<f64>,
pub ki: Option<f64>,
pub kp: Option<f64>,
pub ta: Option<f64>,
pub te: Option<f64>,
pub tf: Option<f64>,
pub vb1max: Option<f64>,
pub vblim: Option<bool>,
pub vbmax: Option<f64>,
pub vrmax: Option<f64>,
pub vrmin: Option<f64>,
}Expand description
Modified old IEEE type 3 excitation system.
Fields§
§base: ExcitationSystemDynamics§exclim: Option<bool>(exclim). true = lower limit of zero is applied to integrator output false = lower limit of zero not applied to integrator output. Typical value = true.
ka: Option<f64>Voltage regulator gain (Ka) (> 0). Typical value = 300.
ke: Option<f64>Exciter constant related to self-excited field (Ke). Typical value = 1.
kf: Option<f64>Excitation control system stabilizer gain (Kf) (>= 0). Typical value = 0,1.
ki: Option<f64>Potential circuit gain coefficient (Ki) (>= 0). Typical value = 4,83.
kp: Option<f64>Potential circuit gain coefficient (Kp) (>= 0). Typical value = 4,37.
ta: Option<f64>Voltage regulator time constant (Ta) (> 0). Typical value = 0,01.
te: Option<f64>Exciter time constant, integration rate associated with exciter control (Te) (> 0). Typical value = 1,83.
tf: Option<f64>Excitation control system stabilizer time constant (Tf) (>= 0). Typical value = 0,675.
vb1max: Option<f64>Available exciter voltage limiter (Vb1max) (> 0). Typical value = 11,63.
vblim: Option<bool>Vb limiter indicator. true = exciter Vbmax limiter is active false = Vb1max is active. Typical value = true.
vbmax: Option<f64>Available exciter voltage limiter (Vbmax) (> 0). Typical value = 11,63.
vrmax: Option<f64>Maximum voltage regulator output (Vrmax) (> ExcDC3A1.vrmin). Typical value = 5.
vrmin: Option<f64>Minimum voltage regulator output (Vrmin) (< 0 and < ExcDC3A1.vrmax). Typical value = 0.