pub struct ExcAVR2 {Show 14 fields
pub base: ExcitationSystemDynamics,
pub e1: Option<f64>,
pub e2: Option<f64>,
pub ka: Option<f64>,
pub kf: Option<f64>,
pub se1: Option<f64>,
pub se2: Option<f64>,
pub ta: Option<f64>,
pub tb: Option<f64>,
pub te: Option<f64>,
pub tf1: Option<f64>,
pub tf2: Option<f64>,
pub vrmn: Option<f64>,
pub vrmx: Option<f64>,
}Expand description
Italian excitation system corresponding to IEEE (1968) type 2 model. It represents an alternator and rotating diodes and electromechanic voltage regulators.
Fields§
§base: ExcitationSystemDynamics§e1: Option<f64>Field voltage value 1 (E1). Typical value = 4,18.
e2: Option<f64>Field voltage value 2 (E2). Typical value = 3,14.
ka: Option<f64>AVR gain (KA). Typical value = 500.
kf: Option<f64>Rate feedback gain (KF). Typical value = 0,12.
se1: Option<f64>Saturation factor at E1 (S[E1]). Typical value = 0.1.
se2: Option<f64>Saturation factor at E2 (S[E2]). Typical value = 0,03.
ta: Option<f64>AVR time constant (TA) (>= 0). Typical value = 0,02.
tb: Option<f64>AVR time constant (TB) (>= 0). Typical value = 0.
te: Option<f64>Exciter time constant (TE) (>= 0). Typical value = 1.
tf1: Option<f64>Rate feedback time constant (TF1) (>= 0). Typical value = 1.
tf2: Option<f64>Rate feedback time constant (TF2) (>= 0). Typical value = 1.
vrmn: Option<f64>Minimum AVR output (VRMN). Typical value = -6.
vrmx: Option<f64>Maximum AVR output (VRMX). Typical value = 7.