pub struct ExcAC1A {Show 23 fields
pub base: ExcitationSystemDynamics,
pub hvlvgates: Option<bool>,
pub ka: Option<f64>,
pub kc: Option<f64>,
pub kd: Option<f64>,
pub ke: Option<f64>,
pub kf: Option<f64>,
pub kf1: Option<f64>,
pub kf2: Option<f64>,
pub ks: Option<f64>,
pub seve1: Option<f64>,
pub seve2: Option<f64>,
pub ta: Option<f64>,
pub tb: Option<f64>,
pub tc: Option<f64>,
pub te: Option<f64>,
pub tf: Option<f64>,
pub vamax: Option<f64>,
pub vamin: Option<f64>,
pub ve1: Option<f64>,
pub ve2: Option<f64>,
pub vrmax: Option<f64>,
pub vrmin: Option<f64>,
}Expand description
Modified IEEE AC1A alternator-supplied rectifier excitation system with different rate feedback source.
Fields§
§base: ExcitationSystemDynamics§hvlvgates: Option<bool>Indicates if both HV gate and LV gate are active (HVLVgates). true = gates are used false = gates are not used. Typical value = true.
ka: Option<f64>Voltage regulator gain (Ka) (> 0). Typical value = 400.
kc: Option<f64>Rectifier loading factor proportional to commutating reactance (Kc) (>= 0). Typical value = 0,2.
kd: Option<f64>Demagnetizing factor, a function of exciter alternator reactances (Kd) (>= 0). Typical value = 0,38.
ke: Option<f64>Exciter constant related to self-excited field (Ke). Typical value = 1.
kf: Option<f64>Excitation control system stabilizer gains (Kf) (>= 0). Typical value = 0,03.
kf1: Option<f64>Coefficient to allow different usage of the model (Kf1) (>= 0). Typical value = 0.
kf2: Option<f64>Coefficient to allow different usage of the model (Kf2) (>= 0). Typical value = 1.
ks: Option<f64>Coefficient to allow different usage of the model-speed coefficient (Ks) (>= 0). Typical value = 0.
seve1: Option<f64>Exciter saturation function value at the corresponding exciter voltage, Ve1, back of commutating reactance (Se[Ve1]) (>= 0). Typical value = 0,1.
seve2: Option<f64>Exciter saturation function value at the corresponding exciter voltage, Ve2, back of commutating reactance (Se[Ve2]) (>= 0). Typical value = 0,03.
ta: Option<f64>Voltage regulator time constant (Ta) (> 0). Typical value = 0,02.
tb: Option<f64>Voltage regulator time constant (Tb) (>= 0). Typical value = 0.
tc: Option<f64>Voltage regulator time constant (Tc) (>= 0). Typical value = 0.
te: Option<f64>Exciter time constant, integration rate associated with exciter control (Te) (> 0). Typical value = 0,8.
tf: Option<f64>Excitation control system stabilizer time constant (Tf) (> 0). Typical value = 1.
vamax: Option<f64>Maximum voltage regulator output (Vamax) (> 0). Typical value = 14,5.
vamin: Option<f64>Minimum voltage regulator output (Vamin) (< 0). Typical value = -14,5.
ve1: Option<f64>Exciter alternator output voltages back of commutating reactance at which saturation is defined (Ve1) (> 0). Typical value = 4,18.
ve2: Option<f64>Exciter alternator output voltages back of commutating reactance at which saturation is defined (Ve2) (> 0). Typical value = 3,14.
vrmax: Option<f64>Maximum voltage regulator outputs (Vrmax) (> 0). Typical value = 6,03.