pub struct WindPlantReactiveControlIEC {Show 19 fields
pub base: IdentifiedObject,
pub dxrefmax: Option<f64>,
pub dxrefmin: Option<f64>,
pub kiwpx: Option<f64>,
pub kiwpxmax: Option<f64>,
pub kiwpxmin: Option<f64>,
pub kpwpx: Option<f64>,
pub kwpqref: Option<f64>,
pub kwpqu: Option<f64>,
pub tuqfilt: Option<f64>,
pub twppfiltq: Option<f64>,
pub twpqfiltq: Option<f64>,
pub twpufiltq: Option<f64>,
pub txft: Option<f64>,
pub txfv: Option<f64>,
pub uwpqdip: Option<f64>,
pub wind_plant_qcontrol_modes_type: Option<UriRef>,
pub xrefmax: Option<f64>,
pub xrefmin: Option<f64>,
}Expand description
Simplified plant voltage and reactive power control model for use with type 3 and type 4 wind turbine models. Reference: IEC 61400-27-1:2015, Annex D.
Fields§
§base: IdentifiedObject§dxrefmax: Option<f64>Maximum positive ramp rate for wind turbine reactive power/voltage reference (dxrefmax) (> WindPlantReactiveControlIEC.dxrefmin). It is a project-dependent parameter.
dxrefmin: Option<f64>Maximum negative ramp rate for wind turbine reactive power/voltage reference (dxrefmin) (< WindPlantReactiveControlIEC.dxrefmax). It is a project-dependent parameter.
kiwpx: Option<f64>Plant Q controller integral gain (KIWPx). It is a project-dependent parameter.
kiwpxmax: Option<f64>Maximum reactive power/voltage reference from integration (KIWPxmax) (> WindPlantReactiveControlIEC.kiwpxmin). It is a project-dependent parameter.
kiwpxmin: Option<f64>Minimum reactive power/voltage reference from integration (KIWPxmin) (< WindPlantReactiveControlIEC.kiwpxmax). It is a project-dependent parameter.
kpwpx: Option<f64>Plant Q controller proportional gain (KPWPx). It is a project-dependent parameter.
kwpqref: Option<f64>Reactive power reference gain (KWPqref). It is a project-dependent parameter.
kwpqu: Option<f64>Plant voltage control droop (KWPqu). It is a project-dependent parameter.
tuqfilt: Option<f64>Filter time constant for voltage-dependent reactive power (Tuqfilt) (>= 0). It is a project-dependent parameter.
twppfiltq: Option<f64>Filter time constant for active power measurement (TWPpfiltq) (>= 0). It is a project-dependent parameter.
twpqfiltq: Option<f64>Filter time constant for reactive power measurement (TWPqfiltq) (>= 0). It is a project-dependent parameter.
twpufiltq: Option<f64>Filter time constant for voltage measurement (TWPufiltq) (>= 0). It is a project-dependent parameter.
txft: Option<f64>Lead time constant in reference value transfer function (Txft) (>= 0). It is a project-dependent parameter.
txfv: Option<f64>Lag time constant in reference value transfer function (Txfv) (>= 0). It is a project-dependent parameter.
uwpqdip: Option<f64>Voltage threshold for UVRT detection in Q control (uWPqdip). It is a project-dependent parameter.
wind_plant_qcontrol_modes_type: Option<UriRef>Reactive power/voltage controller mode (MWPqmode). It is a case-dependent parameter.
xrefmax: Option<f64>Maximum xWTref (qWTref or delta uWTref) request from the plant controller (xrefmax) (> WindPlantReactiveControlIEC.xrefmin). It is a case-dependent parameter.
xrefmin: Option<f64>Minimum xWTref (qWTref or delta uWTref) request from the plant controller (xrefmin) (< WindPlantReactiveControlIEC.xrefmax). It is a project-dependent parameter.
Implementations§
Source§impl WindPlantReactiveControlIEC
impl WindPlantReactiveControlIEC
pub fn from_block(b: &RdfBlock) -> Self
Trait Implementations§
Source§impl Clone for WindPlantReactiveControlIEC
impl Clone for WindPlantReactiveControlIEC
Source§fn clone(&self) -> WindPlantReactiveControlIEC
fn clone(&self) -> WindPlantReactiveControlIEC
1.0.0 (const: unstable) · Source§fn clone_from(&mut self, source: &Self)
fn clone_from(&mut self, source: &Self)
source. Read more