pub struct GovGAST3 {Show 22 fields
pub base: TurbineGovernorDynamics,
pub bca: Option<f64>,
pub bp: Option<f64>,
pub dtc: Option<f64>,
pub ka: Option<f64>,
pub kac: Option<f64>,
pub kca: Option<f64>,
pub ksi: Option<f64>,
pub ky: Option<f64>,
pub mnef: Option<f64>,
pub mxef: Option<f64>,
pub rcmn: Option<f64>,
pub rcmx: Option<f64>,
pub tac: Option<f64>,
pub tc: Option<f64>,
pub td: Option<f64>,
pub tfen: Option<f64>,
pub tg: Option<f64>,
pub tsi: Option<f64>,
pub tt: Option<f64>,
pub ttc: Option<f64>,
pub ty: Option<f64>,
}Expand description
Generic turbogas with acceleration and temperature controller.
Fields§
§base: TurbineGovernorDynamics§bca: Option<f64>Acceleration limit set-point (Bca). Unit = 1/s. Typical value = 0,01.
bp: Option<f64>Droop (bp). Typical value = 0,05.
dtc: Option<f64>Exhaust temperature variation due to fuel flow increasing from 0 to 1 PU (deltaTc). Typical value = 390.
ka: Option<f64>Minimum fuel flow (Ka). Typical value = 0,23.
kac: Option<f64>Fuel system feedback (KAC). Typical value = 0.
kca: Option<f64>Acceleration control integral gain (Kca). Unit = 1/s. Typical value = 100.
ksi: Option<f64>Gain of radiation shield (Ksi). Typical value = 0,8.
ky: Option<f64>Coefficient of transfer function of fuel valve positioner (Ky). Typical value = 1.
mnef: Option<f64>Fuel flow maximum negative error value (MNef). Typical value = -0,05.
mxef: Option<f64>Fuel flow maximum positive error value (MXef). Typical value = 0,05.
rcmn: Option<f64>Minimum fuel flow (RCMN). Typical value = -0,1.
rcmx: Option<f64>Maximum fuel flow (RCMX). Typical value = 1.
tac: Option<f64>Fuel control time constant (Tac) (>= 0). Typical value = 0,1.
tc: Option<f64>Compressor discharge volume time constant (Tc) (>= 0). Typical value = 0,2.
td: Option<f64>Temperature controller derivative gain (Td) (>= 0). Typical value = 3,3.
tfen: Option<f64>Turbine rated exhaust temperature correspondent to Pm=1 PU (Tfen). Typical value = 540.
tg: Option<f64>Time constant of speed governor (Tg) (>= 0). Typical value = 0,05.
tsi: Option<f64>Time constant of radiation shield (Tsi) (>= 0). Typical value = 15.
tt: Option<f64>Temperature controller integration rate (Tt). Typical value = 250.
ttc: Option<f64>Time constant of thermocouple (Ttc) (>= 0). Typical value = 2,5.
ty: Option<f64>Time constant of fuel valve positioner (Ty) (>= 0). Typical value = 0,2.