pub struct PssWECC {Show 19 fields
pub base: PowerSystemStabilizerDynamics,
pub input_signal1type: Option<UriRef>,
pub input_signal2type: Option<UriRef>,
pub k1: Option<f64>,
pub k2: Option<f64>,
pub t1: Option<f64>,
pub t10: Option<f64>,
pub t2: Option<f64>,
pub t3: Option<f64>,
pub t4: Option<f64>,
pub t5: Option<f64>,
pub t6: Option<f64>,
pub t7: Option<f64>,
pub t8: Option<f64>,
pub t9: Option<f64>,
pub vcl: Option<f64>,
pub vcu: Option<f64>,
pub vsmax: Option<f64>,
pub vsmin: Option<f64>,
}Expand description
Dual input power system stabilizer, based on IEEE type 2, with modified output limiter defined by WECC (Western Electricity Coordinating Council, USA).
Fields§
§base: PowerSystemStabilizerDynamics§input_signal1type: Option<UriRef>Type of input signal #1 (rotorAngularFrequencyDeviation, busFrequencyDeviation, generatorElectricalPower, generatorAcceleratingPower, busVoltage, or busVoltageDerivative - shall be different than PssWECC.inputSignal2Type). Typical value = rotorAngularFrequencyDeviation.
input_signal2type: Option<UriRef>Type of input signal #2 (rotorAngularFrequencyDeviation, busFrequencyDeviation, generatorElectricalPower, generatorAcceleratingPower, busVoltage, busVoltageDerivative - shall be different than PssWECC.inputSignal1Type). Typical value = busVoltageDerivative.
k1: Option<f64>Input signal 1 gain (K1). Typical value = 1,13.
k2: Option<f64>Input signal 2 gain (K2). Typical value = 0,0.
t1: Option<f64>Input signal 1 transducer time constant (T1) (>= 0). Typical value = 0,037.
t10: Option<f64>Lag time constant (T10) (>= 0). Typical value = 0.
t2: Option<f64>Input signal 2 transducer time constant (T2) (>= 0). Typical value = 0,0.
t3: Option<f64>Stabilizer washout time constant (T3) (>= 0). Typical value = 9,5.
t4: Option<f64>Stabilizer washout time lag constant (T4) (>= 0). Typical value = 9,5.
t5: Option<f64>Lead time constant (T5) (>= 0). Typical value = 1,7.
t6: Option<f64>Lag time constant (T6) (>= 0). Typical value = 1,5.
t7: Option<f64>Lead time constant (T7) (>= 0). Typical value = 1,7.
t8: Option<f64>Lag time constant (T8) (>= 0). Typical value = 1,5.
t9: Option<f64>Lead time constant (T9) (>= 0). Typical value = 0.
vcl: Option<f64>Minimum value for voltage compensator output (VCL). Typical value = 0.
vcu: Option<f64>Maximum value for voltage compensator output (VCU). Typical value = 0.
vsmax: Option<f64>Maximum output signal (Vsmax) (> PssWECC.vsmin). Typical value = 0,05.
vsmin: Option<f64>Minimum output signal (Vsmin) (< PssWECC.vsmax). Typical value = -0,05.