pub struct GovHydroR {Show 43 fields
pub base: TurbineGovernorDynamics,
pub at: Option<f64>,
pub db1: Option<f64>,
pub db2: Option<f64>,
pub dturb: Option<f64>,
pub eps: Option<f64>,
pub gmax: Option<f64>,
pub gmin: Option<f64>,
pub gv1: Option<f64>,
pub gv2: Option<f64>,
pub gv3: Option<f64>,
pub gv4: Option<f64>,
pub gv5: Option<f64>,
pub gv6: Option<f64>,
pub h0: Option<f64>,
pub input_signal: Option<bool>,
pub kg: Option<f64>,
pub ki: Option<f64>,
pub mwbase: Option<f64>,
pub pgv1: Option<f64>,
pub pgv2: Option<f64>,
pub pgv3: Option<f64>,
pub pgv4: Option<f64>,
pub pgv5: Option<f64>,
pub pgv6: Option<f64>,
pub pmax: Option<f64>,
pub pmin: Option<f64>,
pub qnl: Option<f64>,
pub r: Option<f64>,
pub t1: Option<f64>,
pub t2: Option<f64>,
pub t3: Option<f64>,
pub t4: Option<f64>,
pub t5: Option<f64>,
pub t6: Option<f64>,
pub t7: Option<f64>,
pub t8: Option<f64>,
pub td: Option<f64>,
pub tp: Option<f64>,
pub tt: Option<f64>,
pub tw: Option<f64>,
pub velcl: Option<f64>,
pub velop: Option<f64>,
}Expand description
Fourth order lead-lag governor and hydro turbine.
Fields§
§base: TurbineGovernorDynamics§at: Option<f64>Turbine gain (At). Typical value = 1,2.
db1: Option<f64>Intentional dead-band width (db1). Unit = Hz. Typical value = 0.
db2: Option<f64>Unintentional dead-band (db2). Unit = MW. Typical value = 0.
dturb: Option<f64>Turbine damping factor (Dturb). Typical value = 0,2.
eps: Option<f64>Intentional db hysteresis (eps). Unit = Hz. Typical value = 0.
gmax: Option<f64>Maximum governor output (Gmax) (> GovHydroR.gmin). Typical value = 1,05.
gmin: Option<f64>Minimum governor output (Gmin) (< GovHydroR.gmax). Typical value = -0,05.
gv1: Option<f64>Nonlinear gain point 1, PU gv (Gv1). Typical value = 0.
gv2: Option<f64>Nonlinear gain point 2, PU gv (Gv2). Typical value = 0.
gv3: Option<f64>Nonlinear gain point 3, PU gv (Gv3). Typical value = 0.
gv4: Option<f64>Nonlinear gain point 4, PU gv (Gv4). Typical value = 0.
gv5: Option<f64>Nonlinear gain point 5, PU gv (Gv5). Typical value = 0.
gv6: Option<f64>Nonlinear gain point 6, PU gv (Gv6). Typical value = 0.
h0: Option<f64>Turbine nominal head (H0). Typical value = 1.
input_signal: Option<bool>Input signal switch (Flag). true = Pe input is used false = feedback is received from CV. Flag is normally dependent on Tt. If Tt is zero, Flag is set to false. If Tt is not zero, Flag is set to true. Typical value = true.
kg: Option<f64>Gate servo gain (Kg). Typical value = 2.
ki: Option<f64>Integral gain (Ki). Typical value = 0,5.
mwbase: Option<f64>Base for power values (MWbase) (> 0). Unit = MW.
pgv1: Option<f64>Nonlinear gain point 1, PU power (Pgv1). Typical value = 0.
pgv2: Option<f64>Nonlinear gain point 2, PU power (Pgv2). Typical value = 0.
pgv3: Option<f64>Nonlinear gain point 3, PU power (Pgv3). Typical value = 0.
pgv4: Option<f64>Nonlinear gain point 4, PU power (Pgv4). Typical value = 0.
pgv5: Option<f64>Nonlinear gain point 5, PU power (Pgv5). Typical value = 0.
pgv6: Option<f64>Nonlinear gain point 6, PU power (Pgv6). Typical value = 0.
pmax: Option<f64>Maximum gate opening, PU of MWbase (Pmax) (> GovHydroR.pmin). Typical value = 1.
pmin: Option<f64>Minimum gate opening, PU of MWbase (Pmin) (< GovHydroR.pmax). Typical value = 0.
qnl: Option<f64>No-load turbine flow at nominal head (Qnl). Typical value = 0,08.
r: Option<f64>Steady-state droop (R). Typical value = 0,05.
t1: Option<f64>Lead time constant 1 (T1) (>= 0). Typical value = 1,5.
t2: Option<f64>Lag time constant 1 (T2) (>= 0). Typical value = 0,1.
t3: Option<f64>Lead time constant 2 (T3) (>= 0). Typical value = 1,5.
t4: Option<f64>Lag time constant 2 (T4) (>= 0). Typical value = 0,1.
t5: Option<f64>Lead time constant 3 (T5) (>= 0). Typical value = 0.
t6: Option<f64>Lag time constant 3 (T6) (>= 0). Typical value = 0,05.
t7: Option<f64>Lead time constant 4 (T7) (>= 0). Typical value = 0.
t8: Option<f64>Lag time constant 4 (T8) (>= 0). Typical value = 0,05.
td: Option<f64>Input filter time constant (Td) (>= 0). Typical value = 0,05.
tp: Option<f64>Gate servo time constant (Tp) (>= 0). Typical value = 0,05.
tt: Option<f64>Power feedback time constant (Tt) (>= 0). Typical value = 0.
tw: Option<f64>Water inertia time constant (Tw) (> 0). Typical value = 1.
velcl: Option<f64>Maximum gate closing velocity (Velcl). Unit = PU / s. Typical value = -0,2.
velop: Option<f64>Maximum gate opening velocity (Velop). Unit = PU / s. Typical value = 0,2.