pub struct GovHydro3 {Show 37 fields
pub base: TurbineGovernorDynamics,
pub at: Option<f64>,
pub db1: Option<f64>,
pub db2: Option<f64>,
pub dturb: Option<f64>,
pub eps: Option<f64>,
pub governor_control: Option<bool>,
pub gv1: Option<f64>,
pub gv2: Option<f64>,
pub gv3: Option<f64>,
pub gv4: Option<f64>,
pub gv5: Option<f64>,
pub gv6: Option<f64>,
pub h0: Option<f64>,
pub k1: Option<f64>,
pub k2: Option<f64>,
pub kg: Option<f64>,
pub ki: Option<f64>,
pub mwbase: Option<f64>,
pub pgv1: Option<f64>,
pub pgv2: Option<f64>,
pub pgv3: Option<f64>,
pub pgv4: Option<f64>,
pub pgv5: Option<f64>,
pub pgv6: Option<f64>,
pub pmax: Option<f64>,
pub pmin: Option<f64>,
pub qnl: Option<f64>,
pub relec: Option<f64>,
pub rgate: Option<f64>,
pub td: Option<f64>,
pub tf: Option<f64>,
pub tp: Option<f64>,
pub tt: Option<f64>,
pub tw: Option<f64>,
pub velcl: Option<f64>,
pub velop: Option<f64>,
}Expand description
Modified IEEE hydro governor-turbine. This model differs from that defined in the IEEE modelling guideline paper in that the limits on gate position and velocity do not permit ‘wind up’ of the upstream signals.
Fields§
§base: TurbineGovernorDynamics§at: Option<f64>Turbine gain (At) (>0). Typical value = 1,2.
db1: Option<f64>Intentional dead-band width (db1). Unit = Hz. Typical value = 0.
db2: Option<f64>Unintentional dead-band (db2). Unit = MW. Typical value = 0.
dturb: Option<f64>Turbine damping factor (Dturb). Typical value = 0,2.
eps: Option<f64>Intentional db hysteresis (eps). Unit = Hz. Typical value = 0.
governor_control: Option<bool>Governor control flag (Cflag). true = PID control is active false = double derivative control is active. Typical value = true.
gv1: Option<f64>Nonlinear gain point 1, PU gv (Gv1). Typical value = 0.
gv2: Option<f64>Nonlinear gain point 2, PU gv (Gv2). Typical value = 0.
gv3: Option<f64>Nonlinear gain point 3, PU gv (Gv3). Typical value = 0.
gv4: Option<f64>Nonlinear gain point 4, PU gv (Gv4). Typical value = 0.
gv5: Option<f64>Nonlinear gain point 5, PU gv (Gv5). Typical value = 0.
gv6: Option<f64>Nonlinear gain point 6, PU gv (Gv6). Typical value = 0.
h0: Option<f64>Turbine nominal head (H0). Typical value = 1.
k1: Option<f64>Derivative gain (K1). Typical value = 0,01.
k2: Option<f64>Double derivative gain, if Cflag = -1 (K2). Typical value = 2,5.
kg: Option<f64>Gate servo gain (Kg). Typical value = 2.
ki: Option<f64>Integral gain (Ki). Typical value = 0,5.
mwbase: Option<f64>Base for power values (MWbase) (> 0). Unit = MW.
pgv1: Option<f64>Nonlinear gain point 1, PU power (Pgv1). Typical value = 0.
pgv2: Option<f64>Nonlinear gain point 2, PU power (Pgv2). Typical value = 0.
pgv3: Option<f64>Nonlinear gain point 3, PU power (Pgv3). Typical value = 0.
pgv4: Option<f64>Nonlinear gain point 4, PU power (Pgv4). Typical value = 0.
pgv5: Option<f64>Nonlinear gain point 5, PU power (Pgv5). Typical value = 0.
pgv6: Option<f64>Nonlinear gain point 6, PU power (Pgv6). Typical value = 0.
pmax: Option<f64>Maximum gate opening, PU of MWbase (Pmax) (> GovHydro3.pmin). Typical value = 1.
pmin: Option<f64>Minimum gate opening, PU of MWbase (Pmin) (< GovHydro3.pmax). Typical value = 0.
qnl: Option<f64>No-load turbine flow at nominal head (Qnl). Typical value = 0,08.
relec: Option<f64>Steady-state droop, PU, for electrical power feedback (Relec). Typical value = 0,05.
rgate: Option<f64>Steady-state droop, PU, for governor output feedback (Rgate). Typical value = 0.
td: Option<f64>Input filter time constant (Td) (>= 0). Typical value = 0,05.
tf: Option<f64>Washout time constant (Tf) (>= 0). Typical value = 0,1.
tp: Option<f64>Gate servo time constant (Tp) (>= 0). Typical value = 0,05.
tt: Option<f64>Power feedback time constant (Tt) (>= 0). Typical value = 0,2.
tw: Option<f64>Water inertia time constant (Tw) (>= 0). If = 0, block is bypassed. Typical value = 1.
velcl: Option<f64>Maximum gate closing velocity (Velcl). Unit = PU / s. Typical value = -0,2.
velop: Option<f64>Maximum gate opening velocity (Velop). Unit = PU / s. Typical value = 0,2.