pub struct ExcHU {Show 13 fields
pub base: ExcitationSystemDynamics,
pub ae: Option<f64>,
pub ai: Option<f64>,
pub atr: Option<f64>,
pub emax: Option<f64>,
pub emin: Option<f64>,
pub imax: Option<f64>,
pub imin: Option<f64>,
pub ke: Option<f64>,
pub ki: Option<f64>,
pub te: Option<f64>,
pub ti: Option<f64>,
pub tr: Option<f64>,
}Expand description
Hungarian excitation system, with built-in voltage transducer.
Fields§
§base: ExcitationSystemDynamics§ae: Option<f64>Major loop PI tag gain factor (Ae). Typical value = 3.
ai: Option<f64>Minor loop PI tag gain factor (Ai). Typical value = 22.
atr: Option<f64>AVR constant (Atr). Typical value = 2,19.
emax: Option<f64>Field voltage control signal upper limit on AVR base (Emax) (> ExcHU.emin). Typical value = 0,996.
emin: Option<f64>Field voltage control signal lower limit on AVR base (Emin) (< ExcHU.emax). Typical value = -0,866.
imax: Option<f64>Major loop PI tag output signal upper limit (Imax) (> ExcHU.imin). Typical value = 2,19.
imin: Option<f64>Major loop PI tag output signal lower limit (Imin) (< ExcHU.imax). Typical value = 0,1.
ke: Option<f64>Voltage base conversion constant (Ke). Typical value = 4,666.
ki: Option<f64>Current base conversion constant (Ki). Typical value = 0,21428.
te: Option<f64>Major loop PI tag integration time constant (Te) (>= 0). Typical value = 0,154.
ti: Option<f64>Minor loop PI control tag integration time constant (Ti) (>= 0). Typical value = 0,01333.
tr: Option<f64>Filter time constant (Tr) (>= 0). If a voltage compensator is used in conjunction with this excitation system model, Tr should be set to 0. Typical value = 0,01.