pub struct ExcELIN1 {Show 16 fields
pub base: ExcitationSystemDynamics,
pub dpnf: Option<f64>,
pub efmax: Option<f64>,
pub efmin: Option<f64>,
pub ks1: Option<f64>,
pub ks2: Option<f64>,
pub smax: Option<f64>,
pub tfi: Option<f64>,
pub tnu: Option<f64>,
pub ts1: Option<f64>,
pub ts2: Option<f64>,
pub tsw: Option<f64>,
pub vpi: Option<f64>,
pub vpnf: Option<f64>,
pub vpu: Option<f64>,
pub xe: Option<f64>,
}Expand description
Static PI transformer fed excitation system ELIN (VATECH) - simplified model. This model represents an all-static excitation system. A PI voltage controller establishes a desired field current set point for a proportional current controller. The integrator of the PI controller has a follow-up input to match its signal to the present field current. A power system stabilizer with power input is included in the model.
Fields§
§base: ExcitationSystemDynamics§dpnf: Option<f64>Controller follow up deadband (Dpnf). Typical value = 0.
efmax: Option<f64>Maximum open circuit excitation voltage (Efmax) (> ExcELIN1.efmin). Typical value = 5.
efmin: Option<f64>Minimum open circuit excitation voltage (Efmin) (< ExcELIN1.efmax). Typical value = -5.
ks1: Option<f64>Stabilizer gain 1 (Ks1). Typical value = 0.
ks2: Option<f64>Stabilizer gain 2 (Ks2). Typical value = 0.
smax: Option<f64>Stabilizer limit output (smax). Typical value = 0,1.
tfi: Option<f64>Current transducer time constant (Tfi) (>= 0). Typical value = 0.
tnu: Option<f64>Controller reset time constant (Tnu) (>= 0). Typical value = 2.
ts1: Option<f64>Stabilizer phase lag time constant (Ts1) (>= 0). Typical value = 1.
ts2: Option<f64>Stabilizer filter time constant (Ts2) (>= 0). Typical value = 1.
tsw: Option<f64>Stabilizer parameters (Tsw) (>= 0). Typical value = 3.
vpi: Option<f64>Current controller gain (Vpi). Typical value = 12,45.
vpnf: Option<f64>Controller follow up gain (Vpnf). Typical value = 2.
vpu: Option<f64>Voltage controller proportional gain (Vpu). Typical value = 34,5.
xe: Option<f64>Excitation transformer effective reactance (Xe) (>= 0). Xe represents the regulation of the transformer/rectifier unit. Typical value = 0,06.