pub struct GovSteamIEEE1 {Show 22 fields
pub base: TurbineGovernorDynamics,
pub k: Option<f64>,
pub k1: Option<f64>,
pub k2: Option<f64>,
pub k3: Option<f64>,
pub k4: Option<f64>,
pub k5: Option<f64>,
pub k6: Option<f64>,
pub k7: Option<f64>,
pub k8: Option<f64>,
pub mwbase: Option<f64>,
pub pmax: Option<f64>,
pub pmin: Option<f64>,
pub t1: Option<f64>,
pub t2: Option<f64>,
pub t3: Option<f64>,
pub t4: Option<f64>,
pub t5: Option<f64>,
pub t6: Option<f64>,
pub t7: Option<f64>,
pub uc: Option<f64>,
pub uo: Option<f64>,
}Expand description
IEEE steam turbine governor model. Reference: IEEE Transactions on Power Apparatus and Systems, November/December 1973, Volume PAS-92, Number 6, Dynamic Models for Steam and Hydro Turbines in Power System Studies, page 1904.
Fields§
§base: TurbineGovernorDynamics§k: Option<f64>Governor gain (reciprocal of droop) (K) (> 0). Typical value = 25.
k1: Option<f64>Fraction of HP shaft power after first boiler pass (K1). Typical value = 0,2.
k2: Option<f64>Fraction of LP shaft power after first boiler pass (K2). Typical value = 0.
k3: Option<f64>Fraction of HP shaft power after second boiler pass (K3). Typical value = 0,3.
k4: Option<f64>Fraction of LP shaft power after second boiler pass (K4). Typical value = 0.
k5: Option<f64>Fraction of HP shaft power after third boiler pass (K5). Typical value = 0,5.
k6: Option<f64>Fraction of LP shaft power after third boiler pass (K6). Typical value = 0.
k7: Option<f64>Fraction of HP shaft power after fourth boiler pass (K7). Typical value = 0.
k8: Option<f64>Fraction of LP shaft power after fourth boiler pass (K8). Typical value = 0.
mwbase: Option<f64>Base for power values (MWbase) (> 0). Unit = MW.
pmax: Option<f64>Maximum valve opening (Pmax) (> GovSteamIEEE1.pmin). Typical value = 1.
pmin: Option<f64>Minimum valve opening (Pmin) (>= 0 and < GovSteamIEEE1.pmax). Typical value = 0.
t1: Option<f64>Governor lag time constant (T1) (>= 0). Typical value = 0.
t2: Option<f64>Governor lead time constant (T2) (>= 0). Typical value = 0.
t3: Option<f64>Valve positioner time constant (T3) (> 0). Typical value = 0,1.
t4: Option<f64>Inlet piping/steam bowl time constant (T4) (>= 0). Typical value = 0,3.
t5: Option<f64>Time constant of second boiler pass (T5) (>= 0). Typical value = 5.
t6: Option<f64>Time constant of third boiler pass (T6) (>= 0). Typical value = 0,5.
t7: Option<f64>Time constant of fourth boiler pass (T7) (>= 0). Typical value = 0.
uc: Option<f64>Maximum valve closing velocity (Uc) (< 0). Unit = PU / s. Typical value = -10.
uo: Option<f64>Maximum valve opening velocity (Uo) (> 0). Unit = PU / s. Typical value = 1.
Implementations§
Source§impl GovSteamIEEE1
impl GovSteamIEEE1
pub fn from_block(b: &RdfBlock) -> Self
Trait Implementations§
Source§impl CimElement for GovSteamIEEE1
impl CimElement for GovSteamIEEE1
Source§impl Clone for GovSteamIEEE1
impl Clone for GovSteamIEEE1
Source§fn clone(&self) -> GovSteamIEEE1
fn clone(&self) -> GovSteamIEEE1
1.0.0 (const: unstable) · Source§fn clone_from(&mut self, source: &Self)
fn clone_from(&mut self, source: &Self)
source. Read more