pub struct ACDCConverter {Show 21 fields
pub base: ConductingEquipment,
pub pcc_terminal: Option<MridRef>,
pub base_s: Option<f64>,
pub idc: Option<f64>,
pub idle_loss: Option<f64>,
pub max_p: Option<f64>,
pub max_udc: Option<f64>,
pub min_p: Option<f64>,
pub min_udc: Option<f64>,
pub number_of_valves: Option<i64>,
pub p: Option<f64>,
pub pole_loss_p: Option<f64>,
pub q: Option<f64>,
pub rated_udc: Option<f64>,
pub resistive_loss: Option<f64>,
pub switching_loss: Option<f64>,
pub target_ppcc: Option<f64>,
pub target_udc: Option<f64>,
pub uc: Option<f64>,
pub udc: Option<f64>,
pub valve_u0: Option<f64>,
}Expand description
A unit with valves for three phases, together with unit control equipment, essential protective and switching devices, DC storage capacitors, phase reactors and auxiliaries, if any, used for conversion.
Fields§
§base: ConductingEquipment§pcc_terminal: Option<MridRef>Point of common coupling terminal for this converter DC side. It is typically the terminal on the power transformer (or switch) closest to the AC network.
base_s: Option<f64>Base apparent power of the converter pole. The attribute shall be a positive value.
idc: Option<f64>Converter DC current, also called Id. It is converter’s state variable, result from power flow.
idle_loss: Option<f64>Active power loss in pole at no power transfer. It is converter’s configuration data used in power flow. The attribute shall be a positive value.
max_p: Option<f64>Maximum active power limit. The value is overwritten by values of VsCapabilityCurve, if present.
max_udc: Option<f64>The maximum voltage on the DC side at which the converter should operate. It is converter’s configuration data used in power flow. The attribute shall be a positive value.
min_p: Option<f64>Minimum active power limit. The value is overwritten by values of VsCapabilityCurve, if present.
min_udc: Option<f64>The minimum voltage on the DC side at which the converter should operate. It is converter’s configuration data used in power flow. The attribute shall be a positive value.
number_of_valves: Option<i64>Number of valves in the converter. Used in loss calculations.
p: Option<f64>Active power at the point of common coupling. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for a steady state solution in the case a simplified power flow model is used.
pole_loss_p: Option<f64>The active power loss at a DC Pole = idleLoss + switchingLoss*|Idc| + resitiveLoss*Idc^2. For lossless operation Pdc=Pac. For rectifier operation with losses Pdc=Pac-lossP. For inverter operation with losses Pdc=Pac+lossP. It is converter’s state variable used in power flow. The attribute shall be a positive value.
q: Option<f64>Reactive power at the point of common coupling. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for a steady state solution in the case a simplified power flow model is used.
rated_udc: Option<f64>Rated converter DC voltage, also called UdN. The attribute shall be a positive value. It is converter’s configuration data used in power flow. For instance a bipolar HVDC link with value 200 kV has a 400kV difference between the dc lines.
resistive_loss: Option<f64>It is converter’s configuration data used in power flow. Refer to poleLossP. The attribute shall be a positive value.
switching_loss: Option<f64>Switching losses, relative to the base apparent power ‘baseS’. Refer to poleLossP. The attribute shall be a positive value.
target_ppcc: Option<f64>Real power injection target in AC grid, at point of common coupling. Load sign convention is used, i.e. positive sign means flow out from a node.
target_udc: Option<f64>Target value for DC voltage magnitude. The attribute shall be a positive value.
uc: Option<f64>Line-to-line converter voltage, the voltage at the AC side of the valve. It is converter’s state variable, result from power flow. The attribute shall be a positive value.
udc: Option<f64>Converter voltage at the DC side, also called Ud. It is converter’s state variable, result from power flow. The attribute shall be a positive value.
valve_u0: Option<f64>Valve threshold voltage, also called Uvalve. Forward voltage drop when the valve is conducting. Used in loss calculations, i.e. the switchLoss depend on numberOfValves * valveU0.
Implementations§
Source§impl ACDCConverter
impl ACDCConverter
pub fn from_block(b: &RdfBlock) -> Self
Trait Implementations§
Source§impl CimElement for ACDCConverter
impl CimElement for ACDCConverter
Source§impl Clone for ACDCConverter
impl Clone for ACDCConverter
Source§fn clone(&self) -> ACDCConverter
fn clone(&self) -> ACDCConverter
1.0.0 (const: unstable) · Source§fn clone_from(&mut self, source: &Self)
fn clone_from(&mut self, source: &Self)
source. Read more