pub struct GovSteamFV3 {Show 32 fields
pub base: TurbineGovernorDynamics,
pub gv1: Option<f64>,
pub gv2: Option<f64>,
pub gv3: Option<f64>,
pub gv4: Option<f64>,
pub gv5: Option<f64>,
pub gv6: Option<f64>,
pub k: Option<f64>,
pub k1: Option<f64>,
pub k2: Option<f64>,
pub k3: Option<f64>,
pub mwbase: Option<f64>,
pub pgv1: Option<f64>,
pub pgv2: Option<f64>,
pub pgv3: Option<f64>,
pub pgv4: Option<f64>,
pub pgv5: Option<f64>,
pub pgv6: Option<f64>,
pub pmax: Option<f64>,
pub pmin: Option<f64>,
pub prmax: Option<f64>,
pub t1: Option<f64>,
pub t2: Option<f64>,
pub t3: Option<f64>,
pub t4: Option<f64>,
pub t5: Option<f64>,
pub t6: Option<f64>,
pub ta: Option<f64>,
pub tb: Option<f64>,
pub tc: Option<f64>,
pub uc: Option<f64>,
pub uo: Option<f64>,
}Expand description
Simplified GovSteamIEEE1 steam turbine governor with Prmax limit and fast valving.
Fields§
§base: TurbineGovernorDynamics§gv1: Option<f64>Nonlinear gain valve position point 1 (GV1). Typical value = 0.
gv2: Option<f64>Nonlinear gain valve position point 2 (GV2). Typical value = 0,4.
gv3: Option<f64>Nonlinear gain valve position point 3 (GV3). Typical value = 0,5.
gv4: Option<f64>Nonlinear gain valve position point 4 (GV4). Typical value = 0,6.
gv5: Option<f64>Nonlinear gain valve position point 5 (GV5). Typical value = 1.
gv6: Option<f64>Nonlinear gain valve position point 6 (GV6). Typical value = 0.
k: Option<f64>Governor gain, (reciprocal of droop) (K). Typical value = 20.
k1: Option<f64>Fraction of turbine power developed after first boiler pass (K1). Typical value = 0,2.
k2: Option<f64>Fraction of turbine power developed after second boiler pass (K2). Typical value = 0,2.
k3: Option<f64>Fraction of hp turbine power developed after crossover or third boiler pass (K3). Typical value = 0,6.
mwbase: Option<f64>Base for power values (MWbase) (> 0). Unit = MW.
pgv1: Option<f64>Nonlinear gain power value point 1 (Pgv1). Typical value = 0.
pgv2: Option<f64>Nonlinear gain power value point 2 (Pgv2). Typical value = 0,75.
pgv3: Option<f64>Nonlinear gain power value point 3 (Pgv3). Typical value = 0,91.
pgv4: Option<f64>Nonlinear gain power value point 4 (Pgv4). Typical value = 0,98.
pgv5: Option<f64>Nonlinear gain power value point 5 (Pgv5). Typical value = 1.
pgv6: Option<f64>Nonlinear gain power value point 6 (Pgv6). Typical value = 0.
pmax: Option<f64>Maximum valve opening, PU of MWbase (Pmax) (> GovSteamFV3.pmin). Typical value = 1.
pmin: Option<f64>Minimum valve opening, PU of MWbase (Pmin) (< GovSteamFV3.pmax). Typical value = 0.
prmax: Option<f64>Max. pressure in reheater (Prmax). Typical value = 1.
t1: Option<f64>Governor lead time constant (T1) (>= 0). Typical value = 0.
t2: Option<f64>Governor lag time constant (T2) (>= 0). Typical value = 0.
t3: Option<f64>Valve positioner time constant (T3) (> 0). Typical value = 0.
t4: Option<f64>Inlet piping/steam bowl time constant (T4) (>= 0). Typical value = 0,2.
t5: Option<f64>Time constant of second boiler pass (i.e. reheater) (T5) (> 0 if fast valving is used, otherwise >= 0). Typical value = 0,5.
t6: Option<f64>Time constant of crossover or third boiler pass (T6) (>= 0). Typical value = 10.
ta: Option<f64>Time to close intercept valve (IV) (Ta) (>= 0). Typical value = 0,97.
tb: Option<f64>Time until IV starts to reopen (Tb) (>= 0). Typical value = 0,98.
tc: Option<f64>Time until IV is fully open (Tc) (>= 0). Typical value = 0,99.
uc: Option<f64>Maximum valve closing velocity (Uc). Unit = PU / s. Typical value = -1.
uo: Option<f64>Maximum valve opening velocity (Uo). Unit = PU / s. Typical value = 0,1.
Implementations§
Source§impl GovSteamFV3
impl GovSteamFV3
pub fn from_block(b: &RdfBlock) -> Self
Trait Implementations§
Source§impl CimElement for GovSteamFV3
impl CimElement for GovSteamFV3
Source§impl Clone for GovSteamFV3
impl Clone for GovSteamFV3
Source§fn clone(&self) -> GovSteamFV3
fn clone(&self) -> GovSteamFV3
1.0.0 (const: unstable) · Source§fn clone_from(&mut self, source: &Self)
fn clone_from(&mut self, source: &Self)
source. Read more