pub struct ExcST6B {Show 24 fields
pub base: ExcitationSystemDynamics,
pub ilr: Option<f64>,
pub k1: Option<bool>,
pub kcl: Option<f64>,
pub kff: Option<f64>,
pub kg: Option<f64>,
pub kia: Option<f64>,
pub klr: Option<f64>,
pub km: Option<f64>,
pub kpa: Option<f64>,
pub kvd: Option<f64>,
pub oelin: Option<UriRef>,
pub tg: Option<f64>,
pub ts: Option<f64>,
pub tvd: Option<f64>,
pub vamax: Option<f64>,
pub vamin: Option<f64>,
pub vilim: Option<bool>,
pub vimax: Option<f64>,
pub vimin: Option<f64>,
pub vmult: Option<bool>,
pub vrmax: Option<f64>,
pub vrmin: Option<f64>,
pub xc: Option<f64>,
}Expand description
Modified IEEE ST6B static excitation system with PID controller and optional inner feedback loop.
Fields§
§base: ExcitationSystemDynamics§ilr: Option<f64>Exciter output current limit reference (Ilr) (> 0). Typical value = 4,164.
k1: Option<bool>Selector (K1). true = feedback is from Ifd false = feedback is not from Ifd. Typical value = true.
kcl: Option<f64>Exciter output current limit adjustment (Kcl) (> 0). Typical value = 1,0577.
kff: Option<f64>Pre-control gain constant of the inner loop field regulator (Kff). Typical value = 1.
kg: Option<f64>Feedback gain constant of the inner loop field regulator (Kg) (>= 0). Typical value = 1.
kia: Option<f64>Voltage regulator integral gain (Kia) (> 0). Typical value = 45,094.
klr: Option<f64>Exciter output current limit adjustment (Kcl) (> 0). Typical value = 17,33.
km: Option<f64>Forward gain constant of the inner loop field regulator (Km). Typical value = 1.
kpa: Option<f64>Voltage regulator proportional gain (Kpa) (> 0). Typical value = 18,038.
kvd: Option<f64>Voltage regulator derivative gain (Kvd). Typical value = 0.
oelin: Option<UriRef>OEL input selector (OELin). Typical value = noOELinput (corresponds to OELin = 0 on diagram).
tg: Option<f64>Feedback time constant of inner loop field voltage regulator (Tg) (>= 0). Typical value = 0,02.
ts: Option<f64>Rectifier firing time constant (Ts) (>= 0). Typical value = 0.
tvd: Option<f64>Voltage regulator derivative gain (Tvd) (>= 0). Typical value = 0.
vamax: Option<f64>Maximum voltage regulator output (Vamax) (> 0). Typical value = 4,81.
vamin: Option<f64>Minimum voltage regulator output (Vamin) (< 0). Typical value = -3,85.
vilim: Option<bool>Selector (Vilim). true = Vimin-Vimax limiter is active false = Vimin-Vimax limiter is not active. Typical value = true.
vimax: Option<f64>Maximum voltage regulator input limit (Vimax) (> ExcST6B.vimin). Typical value = 10.
vimin: Option<f64>Minimum voltage regulator input limit (Vimin) (< ExcST6B.vimax). Typical value = -10.
vmult: Option<bool>Selector (vmult). true = multiply regulator output by terminal voltage false = do not multiply regulator output by terminal voltage. Typical value = true.
vrmax: Option<f64>Maximum voltage regulator output (Vrmax) (> 0). Typical value = 4,81.
vrmin: Option<f64>Minimum voltage regulator output (Vrmin) (< 0). Typical value = -3,85.
xc: Option<f64>Excitation source reactance (Xc). Typical value = 0,05.