pub struct ExcRQB {Show 14 fields
pub base: ExcitationSystemDynamics,
pub ki0: Option<f64>,
pub ki1: Option<f64>,
pub klir: Option<f64>,
pub klus: Option<f64>,
pub lsat: Option<f64>,
pub lus: Option<f64>,
pub mesu: Option<f64>,
pub t4m: Option<f64>,
pub tc: Option<f64>,
pub te: Option<f64>,
pub tf: Option<f64>,
pub ucmax: Option<f64>,
pub ucmin: Option<f64>,
}Expand description
Excitation system type RQB (four-loop regulator, r?gulateur quatre boucles, developed in France) primarily used in nuclear or thermal generating units. This excitation system shall be always used together with power system stabilizer type PssRQB.
Fields§
§base: ExcitationSystemDynamics§ki0: Option<f64>Voltage reference input gain (Ki0). Typical value = 12,7.
ki1: Option<f64>Voltage input gain (Ki1). Typical value = -16,8.
klir: Option<f64>OEL input gain (KLIR). Typical value = 12,13.
klus: Option<f64>Limiter gain (KLUS). Typical value = 50.
lsat: Option<f64>Integrator limiter (LSAT). Typical value = 5,73.
lus: Option<f64>Setpoint (LUS). Typical value = 0,12.
mesu: Option<f64>Voltage input time constant (MESU) (>= 0). Typical value = 0,02.
t4m: Option<f64>Input time constant (T4M) (>= 0). Typical value = 5.
tc: Option<f64>Lead lag time constant (TC) (>= 0). Typical value = 0,02.
te: Option<f64>Lead lag time constant (TE) (>= 0). Typical value = 0,22.
tf: Option<f64>Exciter time constant (TF) (>= 0). Typical value = 0,01.
ucmax: Option<f64>Maximum voltage reference limit (UCMAX) (> ExcRQB.ucmin). Typical value = 1,1.
ucmin: Option<f64>Minimum voltage reference limit (UCMIN) (< ExcRQB.ucmax). Typical value = 0,9.