pub struct ExcANS {Show 15 fields
pub base: ExcitationSystemDynamics,
pub blint: Option<i64>,
pub ifmn: Option<f64>,
pub ifmx: Option<f64>,
pub k2: Option<f64>,
pub k3: Option<f64>,
pub kce: Option<f64>,
pub krvecc: Option<i64>,
pub kvfif: Option<i64>,
pub t1: Option<f64>,
pub t2: Option<f64>,
pub t3: Option<f64>,
pub tb: Option<f64>,
pub vrmn: Option<f64>,
pub vrmx: Option<f64>,
}Expand description
Italian excitation system. It represents static field voltage or excitation current feedback excitation system.
Fields§
§base: ExcitationSystemDynamics§blint: Option<i64>Governor control flag (BLINT). 0 = lead-lag regulator 1 = proportional integral regulator. Typical value = 0.
ifmn: Option<f64>Minimum exciter current (IFMN). Typical value = -5,2.
ifmx: Option<f64>Maximum exciter current (IFMX). Typical value = 6,5.
k2: Option<f64>Exciter gain (K2). Typical value = 20.
k3: Option<f64>AVR gain (K3). Typical value = 1000.
kce: Option<f64>Ceiling factor (KCE). Typical value = 1.
krvecc: Option<i64>Feedback enabling (KRVECC). 0 = open loop control 1 = closed loop control. Typical value = 1.
kvfif: Option<i64>Rate feedback signal flag (KVFIF). 0 = output voltage of the exciter 1 = exciter field current. Typical value = 0.
t1: Option<f64>Time constant (T1) (>= 0). Typical value = 20.
t2: Option<f64>Time constant (T2) (>= 0). Typical value = 0,05.
t3: Option<f64>Time constant (T3) (>= 0). Typical value = 1,6.
tb: Option<f64>Exciter time constant (TB) (>= 0). Typical value = 0,04.
vrmn: Option<f64>Minimum AVR output (VRMN). Typical value = -5,2.
vrmx: Option<f64>Maximum AVR output (VRMX). Typical value = 6,5.