pub fn duplicate_in_window(
sequence_number: u8,
initial_sequence_number: u8,
last_sequence_number: u8,
) -> boolExpand description
Return whether sequence_number is a duplicate in the current incomplete window.
This is the modulo-256 predicate from ANSI/ASHRAE 135-2020 Clause 5.4.2.2,
as corrected by Addendum 135-2020ch. initial_sequence_number is the last
sequence number in the previously completed window, and
last_sequence_number is the last segment accepted in order. When those
values are equal, no segment has been accepted in the current window and
the predicate returns false.