Modbus RTU framing for the pamoja SDK.

Modbus is the lingua franca of cheap industrial sensing. Soil NPK probes, energy meters, water-quality transmitters, and pump controllers overwhelmingly speak Modbus over RS485, a serial bus that reaches hundreds of metres down a single cable, which is exactly what a dispersed farm or a rural water network needs. To talk to those devices a node has to put the right bytes on the wire and trust the bytes it gets back, and Modbus RTU pins down precisely what those bytes are.

This crate is that byte layer, with no serial port and no allocation:

  • crc16 - the CRC-16/MODBUS that every RTU frame ends with, the check that lets a receiver reject a frame mangled by electrical noise on a long cable.
  • Pdu - the protocol data unit: a function code and its data. Constructors build the standard requests (read and write coils and registers) so callers never hand-pack a frame, with a raw escape hatch for the function codes this crate does not name.
  • Adu - the RTU application data unit: a unit address, a PDU, and the CRC. It both assembles a frame to send and parses one received, verifying the CRC so a corrupt frame never reaches the application.
  • Response - reads the values back out of a reply: the 16-bit registers of a read-registers response and the packed bits of a read-coils response, plus the Exception a device returns when it refuses a request.

Everything is exact integer and byte work, so the same framing runs on the smallest microcontroller hanging off the bus. Driving the RS485 line itself arrives with the hardware-I/O layer; this is the protocol half ahead of it.

§Examples

use pamoja_modbus::{Adu, Pdu};

// Ask unit 0x11 for three holding registers starting at 0x006B.
let request = Pdu::read_holding_registers(0x006B, 3).to_adu(0x11);
assert_eq!(request.as_bytes(), &[0x11, 0x03, 0x00, 0x6B, 0x00, 0x03, 0x76, 0x87]);

// The device replies with three 16-bit registers; the frame carries its own CRC,
// so a receiver validates it before reading the values.
let on_wire = Adu::from_pdu(0x11, &[0x03, 0x06, 0x02, 0x2B, 0x00, 0x00, 0x00, 0x64])?;
let reply = Adu::parse(on_wire.as_bytes())?;
let registers: Vec<u16> = reply.response().registers()?.collect();
assert_eq!(registers, [0x022B, 0x0000, 0x0064]);

Structs§

Adu
A Modbus RTU frame: a unit address, a PDU, and a trailing CRC.
Coils
An iterator over the bits of a read-coils or read-discrete-inputs response.
Pdu
A Modbus protocol data unit: a function code followed by its data.
Registers
An iterator over the 16-bit registers of a read-registers response.
Response
A borrowed view over a response PDU, for reading the values a device returned.

Enums§

Exception
A Modbus exception code: the reason a device gives for refusing a request.
Function
A Modbus function code, naming the operation a request asks for.
ModbusError
What can go wrong building or reading a Modbus RTU frame.

Functions§

crc16
Computes the CRC-16/MODBUS of a byte slice.