mbrtu-cli 0.1.2

Command-line decoder for Modbus RTU frames, built on mbrtu
mbrtu-cli-0.1.2 is not a library.

mbrtu

CI crates.io docs.rs license: MIT no_std

A no_std, allocation-free parser and encoder for Modbus RTU, the serial-line PDU encoding used by industrial PLCs, sensors, and other field devices.

  • Three function codes, decode and encode: Read Holding Registers, Read Coils, and Write Single Register, plus generic exception response handling that applies to any function code. Every fixture is cross-checked against pymodbus, a real reference implementation, not hand-derived bytes. tests/reference_corpus.rs additionally cross-checks a larger batch of varied frames generated and independently decoded with pymodbus.
  • Requests and responses are separate types. A Modbus request and response for the same function code can be the same length but mean something different, and which one you're looking at isn't always recoverable from the bytes alone - a real Modbus stack always tracks this itself. ModbusRequest and ModbusResponse make that distinction part of the type, rather than guessing.
  • Fuzz-tested with proptest: PDU decode never panics on arbitrary function codes and data, for both directions, and response encode never panics for any count/byte-count value either (see Formal verification for why that side needed checking too).
  • Spec limits enforced on the way in, not just the way out: a request or response quantity/byte-count over the Modbus spec's own maximum (125 registers, 2000 coils) is rejected at decode time, and a response frame carrying the broadcast address (0) - never a real scenario, since Modbus RTU never replies to a broadcast request - is rejected too.
  • no_std, no alloc: works on bare-metal targets with no allocator. Fixed-size arrays (sized to the Modbus spec's own limits: 125 registers, 2000 coils) hold variable-length response data.
  • Zero mandatory dependencies. The CRC-16 and frame codec are hand-rolled.
  • #![forbid(unsafe_code)].
  • Formal verification of the CRC-16, frame layer, and the two count-driven response encoders with Kani, not just tests.

Crates

Crate Description
mbrtu The no_std, no-alloc parser/encoder library.
mbrtu-cli A small command-line decoder (installs as mbrtu).
mbrtu-ffi C FFI bindings, for calling from C/C++.

Quick start

// A request and a response can share a function code and length, so
// decoding is direction-specific - the caller says which one this is.
let request = mbrtu::decode_request(&frame_bytes)?;

let mbrtu::ModbusRequest::ReadHoldingRegisters(req) = request else {
    panic!("expected a Read Holding Registers request");
};
println!("starting_address={} quantity={}", req.starting_address, req.quantity);

Encoding mirrors decoding:

let request = mbrtu::ModbusRequest::WriteSingleRegister(
    mbrtu::message::WriteSingleRegister { address: 0x0001, value: 3 },
);
let mut buf = [0u8; mbrtu::frame::MAX_FRAME_LEN];
let n = mbrtu::encode_request(0x11, &request, &mut buf)?;

Add it to a project with:

cargo add mbrtu

Function code coverage

Code What
1 Read Coils
3 Read Holding Registers
6 Write Single Register
any | 0x80 Exception response

Modbus RTU has no length field or preamble byte of its own - a real receiver finds frame boundaries by inter-character timing (3.5 character times of silence), not by anything encoded in the bytes. Frame::parse therefore treats its whole input slice as exactly one frame, and mbrtu-cli reads one hex-encoded frame per line rather than resyncing through a continuous byte stream.

Frame::parse_response (used by decode_response, mbrtu-cli's response mode, and mbrtu-ffi's mbrtu_decode_response) additionally rejects the broadcast address (0): Modbus RTU never sends a response to a broadcast request, so a response frame from address 0 means something is wrong upstream, not a case a compliant device produces. Frame::parse itself stays permissive, since address 0 is a normal, valid address for a request.

See crates/mbrtu/src/lib.rs for the crate's module layout and crates/mbrtu/src/message for each function code, each with its own reference-verified tests.

C FFI

mbrtu-ffi exposes a C API over the core decoder: opaque request/response handles, a small error enum, and one mbrtu_request_as_<type>/mbrtu_response_as_<type> accessor per function code. See crates/mbrtu-ffi/include/mbrtu.h for the generated header and crates/mbrtu-ffi/tests/smoke.c for a worked example.

Building

This project is built and checked with Nix:

nix develop        # dev shell: toolchain, rust-analyzer
nix flake check -L # fmt, clippy (pedantic), tests, no_std/no_alloc cross-compile, FFI header/smoke checks
nix build           # mbrtu-cli (default package)
nix build .#mbrtu
nix build .#mbrtu-ffi

CI runs the identical nix flake check -L, so there is one source of truth for what "passing" means, locally and in GitHub Actions.

Without Nix, a standard cargo build / cargo test from the workspace root also works with a recent stable Rust toolchain (edition 2024, MSRV tracked in Cargo.toml).

Formal verification

The CRC-16 checksum, frame layer, and the two response types whose wire encoding is driven by a public count/byte-count field (src/crc.rs, src/frame.rs, src/message/read_holding_registers.rs, src/message/read_coils.rs) are proven, not just tested, using Kani, a bounded model checker for Rust. Where the test suite samples inputs, these harnesses (gated behind #[cfg(kani)], so they add nothing to normal builds) prove properties over every input in a bounded space:

  • CRC-16 computation never panics, for any input.
  • Frame parsing never panics on arbitrary bytes, including malformed lengths and checksums, for both Frame::parse and the broadcast-rejecting Frame::parse_response.
  • Encoding a frame and parsing it back recovers the original address, function code, and data exactly.
  • Encoding a ReadHoldingRegistersResponse/ReadCoilsResponse never panics for any count/byte_count value, including ones a real decode would never produce - both fields are public, so a caller can construct one directly with a value wider than the struct's fixed-size backing array. This is exactly the class of bug that shipped in 0.1.0: encode trusted the declared count/byte-count instead of validating it, which either panicked (ReadCoilsResponse) or silently wrote a corrupted, truncated byte count (ReadHoldingRegistersResponse). Fixed in 0.1.1 by giving encode the same bounds check decode already had, and proven here so it can't regress.

Kani requires its own toolchain download (a pinned nightly + CBMC), which needs network access and isn't run inside the hermetic Nix sandbox, so it's a manual step rather than part of nix flake check:

cargo install --locked kani-verifier
cargo kani setup
cargo kani -p mbrtu

License