Batched DC power flow: many scenarios over one topology, one factorization in total.
batch::BatchSolver can reuse only the
symbolic half of its factorization across scenarios, because Newton’s
Jacobian changes numerically at every iteration of every scenario. DC has
no such problem: B depends on the topology alone, so a bus-injection
scenario changes only the right-hand side. That makes batching here a
qualitatively cheaper operation, not merely a parallel one.
The implementation leans on DC being exactly linear rather than re-solving anything:
\[ \theta_s = \theta_{base} + \Delta\theta(\Delta P_s), \qquad P^{f}s = P^{f}{base} + \Delta P^{f}(\Delta P_s) \]
One base solve establishes the phase-shift and reference-angle terms; every
scenario is then that base plus DcSensitivity::response to its own
injection delta. Since response solves against a factorization built once
in DcSensitivity::new, a batch of ten thousand scenarios performs
exactly one numeric factorization.
This is not an approximation, and
tests/dc_batch_test.rs::batch_matches_a_sequential_loop_exactly asserts it
against a plain loop over dc_power_flow to 1e-12.
§Contingencies
Scenario::branch_outages is
rejected here, as it is on the AC path — but for the opposite reason. On AC
it is unimplemented because an outage gives each scenario its own sparsity
pattern. On DC it is unnecessary: an outage’s effect on flows is
DcSensitivity::outage_flows, one solve and no refactorization at all, so
folding it into a scenario type designed around per-bus overrides would be
a worse API than the one that already exists. See
docs/src/powerflow/dc.md.